Are Small Additions Exempt from the Washington Energy Code?
The R502.1.1 Exemption — What It Actually Says
Per WAC 51-11R-50200 R502.1.1: “Additions not greater than 150 square feet in floor area shall not be required to comply with the provisions of Section R406.”
Section R406 is the energy credit section — the part of the code requiring you to earn a certain number of “credits” by choosing efficiency upgrades. For projects exempt from R406, you don’t need to pick credits, fill out the Schedule R worksheet, or calculate energy performance trade-offs.
This is the section wsec.ai’s wizard exists to help with. If your addition qualifies for the R502.1.1 exemption, you don’t need our tool.
What Still Applies (Even for Exempt Additions)
The R502.1.1 exemption is narrow — it only waives R406. The rest of WSEC-R still applies to your addition:
- R402 — Envelope requirements: New walls, floors, and ceilings in your addition must meet minimum R-values for your climate zone.
- R403 — Mechanical systems: Any new mechanical equipment installed must meet current efficiency requirements. Duct insulation requirements still apply.
- R404 — Lighting: New lighting installed in the addition must meet high-efficacy requirements.
Don’t read “R406 exempt” as “WSEC exempt.” You still need code-minimum construction; you just don’t need the credit-selection math.
Examples
- 8’ × 12’ bedroom addition (96 sq ft) — R406 exempt. R402/R403/R404 apply.
- 10’ × 14’ sunroom (140 sq ft) — R406 exempt.
- 12’ × 14’ kitchen bump-out (168 sq ft) — exceeds 150 sq ft, NOT exempt. Falls in the 150–500 tier (2.0 credits required).
- 20’ × 25’ family room addition (500 sq ft) — addition-small tier boundary (2.0 credits required at exactly 500 sq ft).
What Documentation You Still Need for Permitting
Even with the exemption, your local AHJ will likely require:
- Construction drawings showing the addition
- Insulation specifications meeting R402 minimums
- Mechanical equipment specifications (if installing new equipment)
- A statement that the addition qualifies for R502.1.1 exemption — this is usually a simple line on the building permit application or a one-page certification
When the Exemption Doesn’t Apply
The R502.1.1 exemption is ONLY for additions. It does NOT apply to:
- Alterations or renovations of existing space (those have their own Chapter 5 rules)
- New construction of any size
- Repeat applications — you can’t claim two 100 sq ft additions to skirt the threshold; AHJs treat connected work as one project
Related Guides
Addition over 150 sq ft? Check your compliance.
Use the wizard →